Açıklama

tds

Code
N2XBH , YXZ4Z1                   CU/XLPE/STA/HFFR
N2XB(a)H , YXZ4(a)Z1        CU/XLPE/ATA/HFFR
Voltage Rating
0.6/1 kV
Standards
TS IEC 60502-1 , VDE 0276
IEC 60228Conductor
EN 61034Smoke Density
EN 50267Halogen Free
EN 60332-3Flame Retardant (Cat C)
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Solid Copper Conductor (Class 1)
Stranded Copper Conductor (Class 2)
Insulation
XLPE (Cross-linked Polyethylene)
Filler
Halogen Free Filler
Armour
Double Steel Tape (Double Aluminium Tape for one core cables)
Sheath
Halogen Free Sheath
Technical Data
Max. Operating Temperature:90°C
Short  Circuit  Temperature:250°C (max.5 sec)
Bending Radius:15D ( D : Overall Diameter )
Test Voltage:3,5 kV
Application:
These are cables with low dielectric losses used in energy networks in refineries, mines, hotels, schools, tunnels high constructions
hospitals, power plant, data processing centers, business centers where there is a risk of fire.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×10*11,4271,410001,839181
1×16*12,4347,110001,15117109
1×25*14,0468,410000,727150146
1×35*15,2575,410000,524179179
1×50*16,8727,210000,387211218
1×70*18,6940,910000,268257275
1×95*20,51212,810000,193304336
1×120*22,21455,310000,153341388
1×150*24,31776,010000,124377438
1×185*26,42156,010000,0991418501
1×240*29,32728,35000,0754469508
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1,511,5280,8100012,13125
2×2,512,3325,710007,414033
2×413,2386,910004,615243
2×614,2459,310003,086554
2×1016,7613,310001,838775
2×1618,9811,010001,15113100
2×2522,11140,510000,727146136
2×3524,41415,010000,524176165
2×5027,71820,110000,387208201
2×7031,52411,85000,268256255
2×9536,73753,05000,193307314
2×12040,44316,55000,153349364
2×15045,25348,25000,124391416
2×18549,86435,02500,0991442480
2×24056,08146,62500,0754509565
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1,511,9306,6100012,13125
3×2,512,8361,210007,414033
3×413,8436,710004,615243
3×614,8528,010003,086554
3×1017,6720,910001,838775
3×1619,9973,810001,15113100
3×2523,41389,510000,727146136
3×3525,81749,010000,524176165
3×5029,52288,510000,387208201
3×7034,13098,95000,268256255
3×9539,24486,15000,193307314
3×12043,25411,75000,153349364
3×15048,46740,82500,124391416
3×18553,38168,32500,0991442480
3×24060,010367,52500,0754509565
3×30065,812903,12500,0601569643
3×40074,816182,42500,0470637737
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1,512,7346,9100012,13125
4×2,513,6414,310007,414033
4×414,7508,010004,615243
4×615,9622,310003,086554
4×1019,0864,210001,838775
4×1621,61184,310001,15113100
4×2525,41709,210000,727146136
4×3528,32186,510000,524176165
4×5033,02913,510000,387208201
4×7038,34334,85000,268256255
4×9543,25610,85000,193307314
4×12048,16876,55000,153349364
4×15053,48493,92500,124391416
4×18559,410397,82500,0991442480
4×24066,413125,62500,0754509565
4×30073,316472,22500,0601569643
4×40083,020592,82500,0470637737
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1,513,4442,4100012,13125
5×2,514,5534,710007,414033
5×415,7663,610004,615243
5×617,0819,810003,086554
5×1020,51154,610001,838775
5×1623,41596,010001,15113100
5×2527,82334,310000,727146136
5×3531,13009,410000,524176165
5×5036,84477,95000,387208201
5×7042,05912,05000,268256255
5×9548,07752,35000,193307314
5×12053,09438,52500,153349364
5×15059,411797,72500,124391416
5×18565,514319,82500,0991442480
5×24073,818233,12500,0754509565
5×30081,723860,02500,0601569643
5×40092,429875,62500,0470637737
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×2,5+1,513,3395,910007,41 – 12,14033
3×4+2,514,4482,810004,61 – 7,415243
3×6+415,6593,410003,08 – 4,616554
3×10+618,2800,010001,83  – 3,088775
3×16+1020,91099,610001,15 – 1,83113100
3×25+1624,51569,410000,727 – 1,15146136
3×35+1626,61907,510000,524 – 1,15176165
3×50+2530,72555,910000,387 – 0,727208201
3×70+3536,13857,35000,268 – 0,524256255
3×95+5040,85018,85000,193 – 0,387307314
3×120+7045,86213,65000,153 – 0,268349364
3×150+7049,87404,85000,124 – 0,268391416
3×185+9555,59167,62500,0991 – 0,193442480
3×240+12062,011492,12500,0754 – 0,1853509565
3×300+15068,214327,12500,0601 – 0,124569643
3×400+18577,217872,82500,0470 – 0,991637737
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×4+2,515,5561,710004,61 – 7,415243
4×6+416,8695,110003,08 – 4,616554
4×10+619,8957,110001,83 – 3,088775
4×16+1022,81328,710001,15 – 1,83113100
4×25+1626,91917,510000,727 – 1,15146136
4×35+1629,52381,610000,524 – 1,15176165
4×50+2534,63251,25000,387 – 0,727208201
4×70+3540,14771,75000,268 – 0,524256255
4×95+5045,86290,75000,193 – 0,387307314
4×120+7050,97734,82500,153 – 0,268349364
4×150+7056,19368,92500,124 – 0,268391416
4×185+9562,111500,62500,0991 – 0,193442480
4×240+12069,414465,42500,0754 – 0,153509565
4×300+15076,818164,42500,0601 – 0,124569643
4×400+18586,622629,82500,0470 – 0,0991637737
Note 1:
*For N2XB(a)H , YXZ4(a)ZH cables
Note 2:
Current carrying capacities are valid at 30°C ambient temperature.