Açıklama

tds

Code
CYKY            CU/PVC/PVC
Voltage Rating
450/750 V
Standards
CSN 347656 CSN 34615
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Solid Copper Conductor (Class 1)
Stranded Copper Conductor (Class 2)
Insulation
PVC (Polyvinyl Chloride)
Filler
PVC Filler
Armour
–
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:12D ( D : Overall Diameter )
Test Voltage:2,5 kV
Application:
For installation indoors and outdoors, in cable ducts, underground, in power or switching stations,
local energy distributions, industrial plants, where there in no risk of mechanical damage.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1,58,7123,0100012,1–18
2×2,59,9162,810007,41–26
2×411,2226,310004,61–34
2×612,6298,910003,08–44
2×1015,5456,210001,83–61
2×1617,7642,410001,15–82
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1,59,2145,7100012,1–18
3×2,510,4192,310007,41–26
3×411,9277,410004,61–34
3×613,3367,210003,08–44
3×1016,5568,110001,83–61
3×1619,2830,410001,15–82
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1,59,9174,2100012,1–18
4×2,511,3234,110007,41–26
4×413,0343,210004,61–34
4×614,9470,910003,08–44
4×1018,0705,910001,83–61
4×1621,01041,010001,15–82
4×50*33,12803,210000,387––
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1,510,8219,4100012,1–18
5×2,512,3295,310007,41–26
5×414,9460,610004,61–34
5×616,2591,610003,08–44
5×1020,1920,110001,83–61
5×1623,41350,710001,15–82
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
7×1,513,0317,7100012,1–18
7×2,514,7433,710007,41–26
12×1,515,7525,6100012,1–18
12×2,518,0731,110007,41–26
19×1,518,8814,2100012,1–18
19×2,522,11107,710007,41–26
24×1,521,01034,3100012,1–18
24×2,524,31452,910007,41–26
Note :
Current carrying capacities are valid at 30°C ambient temperature.