Code
H07VVH6-F      CU/PVC/PVC
Voltage Rating
450/750 V
Standards
EN 50214 , IEC 60227
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Flexible Copper Conductor (Class 5)
Insulation
PVC (Polyvinyl Chloride)
Filler
–
Armour
–
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:6D ( D : Overall Diameter )
Test Voltage:2,5 kV
Application
It is used conveyor systems, lifting equipments, elevator and submersible pump.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1,511,7 x 4,9121,8100013,3–20
3×2,514,2 x 5,5180,910007,98–27
3×415,7 x 6,4241,110004,95–34
3×617,4 x 7,0309,510003,30–44
3×1021,3 x 8,7468,310001,91–61
3×1624,6 x 9,9689,410001,21–82
3×2529,8 x 11,81071,710000,780–108
3×35*33,1 x 12,91397,510000,554––
3×50*39,0 x 15,11940,810000,386––
3×70*43,8 x 16,72569,910000,272––
3×95*50,1 x 18,83360,710000,206––
3×120*54,6 x 20,34078,05000,161––
3×150*61,0 x 22,55077,75000,129––
3×185*67,8 x 24,86395,05000,106––
3×240*75,4 x 27,37975,45000,0801––
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1,514,6 x 4,9158,3100013,3–20
4×2,517,7 x 5,5229,810007,98–27
4×419,8 x 6,4302,410004,95–34
4×622,0 x 7,0399,810003,30–44
4×1027,2 x 8,7632,710001,91–61
4×1631,5 x 9,9899,110001,21–82
4×2538,4 x 11,81385,710000,780–108
4×35*43,2 x 13,31873,010000,554––
4×50*50,9 x 15,32581,010000,386––
4×70*57,3 x 16,93420,510000,272––
4×95*65,7 x 19,04427,310000,206––
4×120*71,7 x 20,55377,65000,161––
4×150*80,1 x 22,96717,35000,129––
4×185*89,2 x 25,28465,05000,106––
4×240*99,3 x 27,710561,75000,0801––
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1,517,5 x 4,9191,7100013,3–20
5×2,521,2 x 5,5278,910007,98–27
5×423,8 x 6,4369,210004,95–34
5×626,6 x 7,0490,410003,30–44
5×1033,1 x 8,7779,010001,91–61
5×1638,3 x 9,91092,010001,21–82
5×2547,0 x 11,81715,710000,780–108
5×35*53,3 x 13,52344,910000,554––
5×50*62,8 x 15,73247,710000,386––
5×70*70,8 x 17,34251,810000,272––
5×95*81,4 x 19,45562,510000,206––
5×120*88,8 x 20,96753,95000,161––
5×150*99,2 x 23,18401,95000,129––
5×185*110,7 x 25,410588,55000,106––
5×240*123,2 x 27,913211,85000,0801––
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×16+10*30,5 x 10,1968,810001,21 – 1,91–82
3×25+16*36,7 x 11,81461,910000,780 – 1,21–108
3×35+16*40,8 x 13,51880,410000,554 – 1,21––
3×50+25*48,4 x 15,72616,210000,386 – 0,780––
3×70+35*54,3 x 17,33437,310000,272 – 0,554––
3×95+50*62,4 x 19,44534,010000,206 – 0,386––
3×120+70*68,5 x 20,95499,45000,161 – 0,272––
3×150+70*74,9 x 23,16553,45000,129 – 0,272––
3×185+95*83,9 x 25,48197,75000,106 – 0,206––
3×240+120*92,9 x 27,910164,15000,0801 – 0,161––
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
8×1,527,1 x 4,9298,650013,3–20
10×1,532,9 x 4,9364,850013,3–20
12×1,539,7 x 4,9439,450013,3–20
16×1,552,2 x 4,9580,150013,3–20
Note 1:
* For A07VVH6-F Cables
Note 2:
Current carrying capacities are valid at 30°C ambient temperature