Açıklama

tds

Code
N2XRH , YXZ2Z1                    CU/XLPE/SWA/HFFR
N2XR(a)H , YXZ2(a)Z1         CU/XLPE/AWA/HFFR
Voltage Rating
0.6/1 kV
Standards
TS HD 604 S1-KISIM 5G , VDE 0276
IEC 60228Conductor
EN 61034Smoke Density
EN 50267Halogen Free
EN 60332-3Flame Retardant (Cat C)
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Solid Copper Conductor (Class 1)
Stranded Copper Conductor (Class 2)
Insulation
XLPE (Cross-linked Polyethylene)
Filler
Halogen Free Filler
Armour
Round Steel Wire (Aluminium Wire for One Core Cables)
Sheath
Halogen Free Sheath
Technical Data
Max. Operating Temperature:90°C
Short  Circuit  Temperature:250°C (max.5 sec)
Bending Radius:15D ( D : Overall Diameter )
Test Voltage:3,5 kV
Application
These are cables with low dielectric losses used in energy networks in refineries, mines, hotels, schools,
 tunnels high constructions hospitals, power plant, data processing centers, business centers where there is a risk of fire.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×4*11,7222,210004,615547
1×6*12,2254,910003,086859
1×10*13,5316,010001,839181
1×16*14,5394,610001,15117109
1×25*16,1523,410000,727150146
1×35*17,3633,510000,524179179
1×50*18,9786,610000,387211218
1×70*20,71007,710000,268257275
1×95*23,31323,810000,193304336
1×120*25,01582,510000,153341388
1×150*27,11917,810000,124377438
1×185*29,42331,710000,0991418501
1×240*32,32908,65000,0754469508
1×300*36,33732,95000,0601514654
1×400*40,34627,75000,0470565733
1×500*44,25863,22500,0366623825
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1,512,7303,2100012,13125
2×2,513,5348,110007,414033
2×414,4421,510004,615243
2×615,4485,610003,086554
2×1018,8753,510001,838775
2×1621,0968,410001,15113100
2×2524,91456,410000,727146136
2×3527,21741,510000,524176165
2×5030,72227,510000,387208201
2×7035,43039,85000,268256255
2×9539,93905,75000,193307314
2×12043,64673,55000,153349364
2×15049,56183,35000,124391416
2×18554,07242,32500,0991442480
2×24060,38972,52500,0754509565
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1,513,1332,8100012,13125
3×2,514,0386,910007,414033
3×2,5 rm14,5411,810007,414033
3×415,0467,910004,615243
3×4 rm15,5496,610004,615243
3×616,9644,010003,086554
3×6 rm17,7692,710003,086554
3×1019,7873,710001,838775
3×1622,71253,110001,15113100
3×2526,11727,910000,727146136
3×3528,82145,610000,524176165
3×5032,52718,410000,387208201
3×7038,03812,610000,268256255
3×9542,44879,95000,193307314
3×12047,56154,75000,153349364
3×15052,67609,45000,124391416
3×18557,59083,62500,0991442480
3×24064,311135,92500,0754509565
3×30070,113537,82500,0601569643
3×40080,517835,02500,0470637737
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×16+1021,91148,010001,15 – 1,83113100
2×25+1625,01572,710000,727 – 1,15146136
2×35+1626,71822,710000,524 – 1,15176165
3×16+1023,71406,610001,15 – 1,83113100
3×25+1627,31904,61000 0,727 – 1,15146136
3×35+1629,62305,810000,524 – 1,15176165
3×50+2534,63224,810000,387 – 0,727208201
3×70+3539,34333,05000,268 – 0,524256255
3×95+5044,05508,45000,193 – 0,387307314
3×120+7050,17161,25000,153 – 0,268349364
3×150+7054,08358,32500,124 – 0,268391416
3×185+9559,810324,32500,0991 – 0,193442480
3×240+12066,212527,82500,0754 – 0,153509565
3×300+15073,816534,92500,0601 – 0,124569643
3×400+18582,919848,92500,0470 – 0,0991637737
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1,513,9375,5100012,13125
4×2,514,8441,310007,414033
4×416,8627,110004,615243
4×618,0768,310003,086554
4×6 rm18,9803,410003,086554
4×1021,11025,110001,838775
4×1624,41481,610001,15113100
4×2528,42077,510000,727146136
4×3531,32596,410000,524176165
4×5036,83586,210000,387208201
4×7041,54689,35000,268256255
4×9547,56355,95000,193307314
4×12052,47732,25000,153349364
4×15057,79389,32500,124391416
4×18563,611185,72500,0991442480
4×24070,713756,62500,0754509565
4×30079,018153,92500,0601569643
4×40088,722018,72500,0470637737
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1,514,6458,2100012,13125
5×2,516,6642,110007,414033
5×417,8775,010004,615243
5×619,1935,010003,086554
5×1023,31406,810001,838775
5×1626,21910,310001,15113100
5×2530,82708,110000,727146136
5×3534,93606,210000,524176165
5×5040,04713,25000,387208201
5×7046,36534,25000,268256255
5×9552,28404,45000,193307314
5×12057,310209,72500,153349364
5×15063,612392,82500,124391416
5×18569,814783,62500,0991442480
5×24079,419694,82500,0754509565
5×30086,724073,62500,0601569643
5×40097,529585,42500,0470637737
7×2,5 rm18,4731,010007,4121,517,0
24×2,526,41638,710007,4112,510,5
Note 1:
*For N2XR(a)H , YXZ2(a)Z1 cables
Note 2:
Current carrying capacities are valid at 30°C ambient temperature