Açıklama

tds

Code
YXV-F , N2XY-F, 2XY-F              CU/XLPE/PVC

 

 Voltage Rating                                                                                                                                                                                                                    
0.6/1 kV

 

 Standards                                                                                                                                                                                                                             
IEC 60502-1 , VDE 0276
IEC 60228

 

 Reaction to Fire Classification ( CPR )                                                                                                                                                                               
EN 60332-1-2

 

Conductor Flame Retardant

 

 Conductor                                                                                                                                                                                                                             
Flexible Copper Conductor (Class 5)

 

 Insulation                                                                                                                                                                                                                             
XLPE (Cross-linked Polyethylene)

 

 Filler                                                                                                                                                                                                                                       
PVC Filler

 

 Armour                                                                                                                                                                                                                                 

 

 Sheath                                                                                                                                                                                                                                   
PVC (Polyvinyl Chloride)

 

 Technical Data                                                                                                                                                                                                                     
Max. Operating Temperature:90°C
Short Circuit Temperature:250°C (max.5 sec)
Bending Radius:6D ( D : Overall Diameter )
Test Voltage:3,5 kV

 

 Application:                                                                                                                                                                                                                          
For installation indoors and outdoors, in cable ducts, underground , in power or switching stations, local energy distributions,
industrial plants where there is a risk of mechanical damage. Suitable for comparatively high maximum permissible
conductor temperature.

 

Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×46,694,510004,955444
1×67,2118,810003,306756
1×108,1163,010001,918977
1×169,1223,310001,21115102
1×2510,8337,010000,780148138
1×3511,9446,310000,554177170
1×5013,5597,610000,386209207
1×7015,4803,010000,272256263
1×9517,21044,510000,206307325
1×12019,01292,610000,161349380
1×15021,21591,910000,129393437
1×18523,62013,710000,106445507
1×24026,12517,85000,0801517604
1×30028,73114,15000,0641663697
1×40032,84211,95000,0486749811
1×50037,35376,95000,0384843940
1×63041,76875,45000,02879351083

 

Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1,510,4181,5100013,33124
2×2,511,3221,010007,984032
2×412,3270,310004,955242
2×613,4336,010003,306453
2×1015,2444,410001,918674
2×1617,1601,510001,2111298
2×2520,6911,010000,780145133
2×3523,01201,110000,554174162
2×5026,21603,610000,386206197
2×7030,52197,45000,272254250
2×9534,22839,45000,206305308
2×12038,23522,65000,161348359
2×15042,54356,35000,129392412
2×18547,85546,52500,106444475
2×24052,86885,82500,0801517564

 

Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1,510,9191,6100013,33124
3×2,511,8238,210007,984032
3×412,9300,610004,955242
3×614,1385,110003,306453
3×1016,1539,410001,918674
3×1618,1742,210001,2111298
3×2521,91142,910000,780145133
3×3524,51528,210000,554174162
3×5028,12066,810000,386206197
3×7032,72842,610000,272254250
3×9536,63636,75000,206305308
3×12040,94556,35000,161348359
3×15045,65640,95000,129392412
3×18551,37188,02500,106444475
3×24056,68940,22500,0801517564

 

Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×16+1019,2859,910001,21 – 1,9111298
3×25+1622,91303,010000,780 – 1,21145133
3×35+1625,01668,410000,554 – 1,21174162
3×50+2529,32318,310000,386 – 0,780206197
3×70+3533,93182,65000,272 – 0,554254250
3×95+5038,34174,45000,206 – 0,386305308
3×120+7043,25288,15000,161 – 0,272348359
3×150+7047,06343,22500,129 – 0,272392412
3×185+9553,08104,62500,106 – 0,206444475
3×240+12058,610088,02500,0801 – 0,161517564
3×300+15065,112540,02500,0641 – 0,129585649
3×400+18574,116734,82500,0486 – 0,106671761

 

Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1,511,6222,4100013,33124
4×2,512,7283,910007,984032
4×413,9394,910004,955242
4×615,3471,210003,306453
4×1017,4661,010001,918674
4×1619,8929,310001,2111298
4×2524,01438,910000,780145133
4×3526,91927,910000,554174162
4×5031,12664,810000,386206197
4×7036,13678,25000,272254250
4×9540,64772,15000,206305308
4×12045,45929,25000,161348359
4×15050,57387,52500,129392412
4×18556,99383,32500,106444475
4×24062,911691,62500,0801517564
4×30069,714482,82500,0641585649
4×40079,619545,02500,0486671761

 

Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1,512,4313,2100013,33124
5×2,513,6401,310007,984032
5×415,0517,510004,955242
5×616,5672,510003,306453
5×1018,9958,710001,918674
5×1621,51343,310001,2111298
5×2526,22093,410000,780145133
5×3529,62818,210000,554174162
5×5034,33873,85000,386206197
5×7039,95292,05000,272254250
5×9544,86832,55000,206305308
5×12050,18530,32500,161348359
5×15055,910627,12500,129392412
5×18563,013503,92500,106444475
5×24069,616811,92500,0801517564
5×30077,220866,72500,0641585649
5×40088,328068,72500,0486671761
7×1,513,4312,9100013,316,012,5
12×1,516,1467,5100013,3
12×2,517,8627,110007,98
24×1,520,9800,6100013,39,58,0

 

Note :
Current carrying capacities are valid at 30°C ambient temperature.