Açıklama

tds

Code
YVZ4V , NYBY , SZRMKVM       CU/PVC/STA/PVC
YVZ4(a)V , NYB(a)Y                    CU/PVC/ATA/PVC
Voltage Rating
0.6/1 kV
Standards
IEC 60502-1 , VDE 0276
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Solid Copper Conductor (Class 1)
Stranded Copper Conductor (Class 2)
Insulation
PVC (Polyvinyl Chloride)
Filler
PVC Filler
Armour
Double Steel Tape (Double Aluminium Tape for one core cables)
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:15D ( D : Overall Diameter )
Test Voltage:3,5 kV
Application:
Locations under mechanical stress, underground, in power and switching stations, industrial plants.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×25*15,0495,510000,727139119
1×35*16,2607,310000,524166146
1×50*18,0781,510000,387196177
1×70*19,6995,710000,268238221
1×95*21,91301,810000,193281270
1×120*23,41547,010000,153315310
1×150*25,41877,710000,124347350
1×185*27,72287,610000,0991385399
1×240*30,82894,45000,0754432462
1×300*34,23650,55000,0601473519
1×400*39,44726,25000,0470521583
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1,512,3297,3100012,12719,5
2×2,513,1343,510007,413626
2×414,8444,710004,614734
2×615,8520,710003,085944
2×1018,3710,910001,837960
2×1620,5922,610001,1510280
2×2523,71267,210000,727133108
2×3526,01564,110000,524160132
2×5029,82061,610000,387190160
2×7033,72682,65000,268234202
2×9539,94074,55000,193280249
2×12043,24806,95000,153319289
2×15048,05892,15000,124357329
2×18552,57128,12500,0991402377
2×24059,28981,02500,0754463443
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1,512,8328,5100012,12719,5
3×2,513,6385,310007,413626
3×415,5506,310004,614734
3×616,5602,210003,085944
3×1019,3853,910001,837960
3×1621,61127,910001,1510280
3×2525,11541,710000,727133108
3×3527,61924,810000,524160132
3×5032,22611,110000,387190160
3×7035,93375,15000,268234202
3×9542,55056,15000,193280249
3×12046,56083,95000,153319289
3×15051,37371,12500,124357329
3×18556,69035,02500,0991402377
3×24063,411335,22500,0754463443
3×30069,613983,42500,0601518504
3×40078,717451,72500,0470579577
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×4+2,516,0642,110004,61 – 7,414734
3×16+1022,81258,510001,15 – 1,8310280
3×25+1626,31756,410000,727 – 1,15133108
3×35+1628,52132,010000,524 – 1,15160132
3×50+2533,52911,810000,387 – 0,727190160
3×70+3538,74283,55000,268 – 0,524234202
3×95+5044,75703,65000,193 – 0,387280249
3×120+7048,86868,05000,153 – 0,268319289
3×150+7052,88099,15000,124 – 0,268357329
3×150+1050,67493,75000,124 – 1,83357329
3×185+9558,810083,32500,0991 – 0,193402377
3×240+12065,512565,22500,0754 – 0,153463443
3×300+15072,515601,12500,0601 – 0,124518504
3×400+18582,420399,92500,0470 – 0,0991579577
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×16+2×1024,61533,810001,15 – 1,8310280
3×25+2×1633,12137,810000,727 – 1,15133108
3×35+2×1630,52496,010000,524 – 1,15160132
3×50+2×2536,83759,35000,387 – 0,727190160
3×70+2×3540,94805,15000,268 – 0,524234202
3×95+2×5047,46412,85000,193 – 0,387280249
3×120+2×7051,97811,62500,153 – 0,268319289
3×150+2×7055,99078,22500,124 – 0,268357329
3×185+2×9562,311343,12500,0991 – 0,193402377
3×240+2×12069,114071,42500,0754 – 0,153463443
3×300+2×15077,918545,42500,0601 – 0,124518504
3×400+2×18586,822806,02500,0470 – 0,0991579577
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1,513,5373,5100012,12719,5
4×2,514,5443,510007,413626
4×416,6591,310004,614734
4×617,7711,410003,085944
4×1020,81000,510001,837960
4×1623,41339,310001,1510280
4×2527,41891,510000,727133108
4×3530,32396,710000,524160132
4×5035,53256,310000,387190160
4×7040,94256,35000,268234202
4×9547,36309,05000,193280249
4×12051,37571,95000,153319289
4×15057,09254,52500,124357329
4×18562,511344,62500,0991402377
4×24070,114273,82500,0754463443
4×30077,517802,12500,0601518504
4×40088,523283,52500,0470579577
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1,514,4428,1100012,12719,5
5×2,515,4513,610007,413626
5×417,7694,710004,614734
5×619,0843,110003,085944
5×1022,51201,310001,837960
5×1625,41623,710001,1510280
5×2530,02332,310000,727133108
5×3533,72978,610000,524160132
5×5040,24574,75000,387190160
5×7045,35925,15000,268234202
5×9551,97841,55000,193280249
5×12056,89451,62500,153319289
5×15062,711547,62500,124357329
5×18568,914104,72500,0991402377
5×24077,717927,32500,0754463443
5×30086,823411,62500,0601518504
5×40098,029111,62500,0470579577
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
7×1,515,4495,3100012,1
7×2,516,5594,810007,41
7×419,2825,810004,61
7×620,61028,610003,08
10×1,517,1630,4100012,1
10×2,518,5779,210007,41
10×421,71086,910004,61
14×1,519,1789,5100012,1
14×2,520,7989,310007,41
14×424,51401,010004,61
19×1,521,2977,4100012,1
19×2,523,11240,210007,41
19×427,41778,710004,61
27×1,524,01271,750012,1
27×2,526,31634,85007,41
27×432,32454,25004,61
30×1,525,01377,250012,1
30×2,527,41776,85007,41
30×433,72633,95004,61
48×1,530,62139,650012,1
Note 1:
* For  YVZ4(a)V , NYB(a)Y cables
Note 2:
Current carrying capacities are valid at 30°C ambient temperature.