Açıklama

tds

Code
YAXZ4V ,  NA2XBY ,                  AL/XLPE/STA/PVC
YAXZ4(a)V ,  NA2XB(a)Y ,       AL/XLPE/ATA/PVC
Voltage Rating
0.6/1 kV
Standards
TS IEC 60502-1 , VDE 0276
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Stranded Aluminum Conductor (Class 2)
Insulation
XLPE (Cross-linked Polyethylene)
Filler
PVC Filler
Armour
Double Steel Tape (Double Aluminium Tape for one core cables)
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:90°C
Short  Circuit  Temperature:250°C (max.5 sec)
Bending Radius:15D ( D : Overall Diameter )
Test Voltage:3,5 kV
Application:
For installation indoors and outdoors, in cable ducts, underground , in power or switching stations, local energy distribution
industrial plants, where there is no risk of mechanical damage.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×10 *11,0204,210003,08
1×16 *12,1243,210001,91
1×25 *13,7304,810001,20116112
1×35 *14,7357,510000,868138137
1×50 *16,1419,710000,641164169
1×70 *18,2523,010000,443201214
1×95 *19,7631,910000,320240263
1×120 *21,2734,310000,253272308
1×150 *24,2985,810000,206303349
1×185 *26,41163,010000,164340401
1×240 *28,91394,15000,125387469
1×300 *32,11727,05000,100430535
1×400 *35,72147,65000,0778479615
1×500 *39,42577,52500,0605531700
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1016,2502,310003,08
2×1618,2626,910001,91
2×2521,3830,110001,20113104
2×3523,41005,210000,868136128
2×5026,21227,010000,641159152
2×7030,61660,05000,443197194
2×9534,92517,95000,320236239
2×12038,22962,15000,253269278
2×15043,83697,35000,206302316
2×18548,44425,22500,164342365
2×24053,55383,42500,125397430
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1017,0548,710003,08
3×1619,1687,210001,91
3×2522,5918,010001,20113104
3×3524,81125,610000,868136128
3×5027,91372,410000,641159152
3×7033,11871,65000,443197194
3×9537,32840,85000,320236239
3×12040,83403,45000,253269278
3×15046,84180,02500,206302316
3×18551,84985,92500,164342365
3×24057,76099,82500,125397430
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×16+1020,1755,010001,91 – 3,08
3×25+1623,61008,810001,20 – 1,91113104
3×35+1625,41187,710000,868 – 1,91136128
3×50+2529,11493,410000,641 – 1,20159152
3×70+3534,32022,95000,443 – 0,868197194
3×95+5038,73021,95000,320 – 0,641236239
3×120+7043,53757,55000,253 – 0,443269278
3×150+7048,24369,25000,206 – 0,443302316
3×185+9553,85379,22500,164 – 0,320342365
3×240+12059,46463,22500,125 – 0,253397430
3×300+15066,07898,12500,100 – 0,206454506
3×400+18575,010971,82500,0778 – 0,164520575
3×70+5035,22114,15000,443 – 0,641197194
3×240+9558,56324,32500,125 – 0,320397430
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1018,4634,910003,08
4×1620,7798,510001,91
4×2524,51074,910001,20113104
4×3527,11322,410000,868136128
4×5031,11700,510000,641159152
4×7037,22757,55000,443197194
4×9541,13366,35000,320236239
4×12045,54058,85000,253269278
4×15051,74969,22500,206302316
4×18557,76087,82500,164342365
4×24063,97335,62500,125397430
4×30071,09095,22500,100454506
4×40080,412480,12500,0778520575
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1019,8732,410003,08
5×1622,4934,610001,91
5×2526,71279,210001,20113104
5×3529,71604,710000,868136128
5×5034,82509,75000,641159152
5×7040,83300,15000,443197194
5×9545,64128,85000,320236239
5×12050,14920,02500,253269278
5×15057,46153,62500,206302316
5×18563,67435,62500,164342365
5×24070,59002,12500,125397430
5×30079,112241,32500,100454506
5×40088,815270,72500,0778520575
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×16+2×1021,4846,410001,91 – 3,08
3×25+2×1625,01124,810001,20 – 1,91113104
3×35+2×1626,71294,110000,868 – 1,91136128
3×50+2×2531,62088,210000,641 – 1,20159152
3×70+2×3536,82705,95000,443 – 0,868197194
3×95+2×5041,03357,15000,320 – 0,641236239
3×120+2×7046,54190,65000,253 – 0,443269278
3×150+2×7050,74798,85000,206 – 0,443302316
3×185+2×9556,65911,92500,164 – 0,320342365
3×240+2×12062,57112,72500,125 – 0,253397430
3×300+2×15070,49668,52500,100 – 0,206454506
3×400+2×18579,111018,12500,0778 – 0,164520575
Note 1:
* For YAXZ4(a)V , NA2XB(a)Y cables
Note 2:
Current carrying capacities are valid at 30°C ambient temperature.