Açıklama

tds

Code
NA2XY , YAXV            AL/XLPE/PVC
Voltage Rating
0.6/1 kV
Standards
TS IEC 60502-1 , VDE 0276, SI 1516.1
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Stranded Aluminum Conductor (Class 2)
Insulation
XLPE (Cross-linked Polyethylene)
Filler
PVC Filler
Armour
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:90°C
Short  Circuit  Temperature:250°C (max.5 sec)
Bending Radius:12D ( D : Overall Diameter )
Test Voltage:3,5 kV
Application:
For installation indoors and outdoors, in cable ducts, underground , in power or switching stations, local energy distribution
industrial plants, where there is no risk of mechanical damage. Suitable for comparatively high maximum pemissible
conductor temperature.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×107,989,710003,08
1×168,9118,710001,91
1×2510,5155,810001,20114106
1×3511,5201,210000,868136130
1×5012,8239,410000,641162161
1×7015,0314,110000,443199204
1×9516,6416,410000,320238252
1×12018,3499,310000,253272295
1×15020,9611,610000,206305339
1×18523,2783,510000,164347395
1×24025,7960,010000,125404472
1×30028,51216,210000,100457547
1×40032,11573,510000,0778525643
1×50035,81942,15000,0605601754
1×63040,32440,05000,0469687882
1×80044,73035,35000,03677761019
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1014,8320,310003,08
2×1616,8418,910001,91
2×2519,9589,010001,20112102
2×3522,2735,310000,868135126
2×5025,2934,710000,641158149
2×7029,71284,010000,443196191
2×9532,91618,910000,320234234
2×12036,62005,710000,253268273
2×15041,72533,710000,206300311
2×18546,83170,910000,164342360
2×24051,83932,55000,125398427
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1015,6360,510003,08
3×1617,7488,510001,91
3×2521,1688,810001,20112102
3×3523,6828,210000,868135126
3×5026,61022,510000,641158149
3×7031,91449,210000,443196191
3×9535,31849,310000,320234234
3×12039,32279,610000,253268273
3×15044,92862,05000,206300311
3×18550,33513,15000,164342360
3×24055,84191,05000,125398427
3×30062,65368,12500,100457507
3×40070,47707,12500,0778529600
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×16+1018,7528,910001,91 – 3,08
3×25+1622,2689,710001,20 – 1,91112102
3×35+1624,3872,310000,868 – 1,91135126
3×35+2525,2917,510000,868 – 1,20135126
3×50+2527,71088,210000,641 – 1,20158149
3×50+3528,51160,810000,641 – 0,868158149
3×70+3532,91499,410000,443 – 0,868196191
3×70+5033,81592,510000,443 – 0,641196191
3×95+5036,81940,710000,320 – 0,641234234
3×120+7041,52385,75000,253 – 0,443268273
3×150+7046,22951,35000,206 – 0,443300311
3×185+7050,83747,15000,164 – 0,443342360
3×185+9551,73798,15000,164 – 0,320342360
3×240+9556,44638,72500,125 – 0,320398427
3×240+12057,44642,62500,125 – 0,253398427
3×300+12062,85874,52500,100 – 0,253457507
3×300+15064,35708,72500,100 – 0,206457507
3×400+18572,37604,92500,0778 – 0,164529600
3×500+24080,69705,12500,0605 – 0,125609695
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1017,0410,810003,08
4×1619,3553,110001,91
4×2523,1788,410001,20112102
4×3525,8979,010000,868135126
4×5029,41216,010000,641158149
4×7035,21682,510000,443196191
4×9539,12178,610000,320234234
4×12043,62704,45000,253268273
4×15049,83382,85000,206300311
4×18555,84285,75000,164342360
4×24061,95104,12500,125398427
4×30069,16591,22500,100457507
4×40077,88644,32500,0778529600
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1018,4599,410003,08
5×1621,0755,310001,91
5×2525,31031,310001,20112102
5×3528,41328,810000,868135126
5×5032,41614,010000,641158149
5×7038,92128,35000,443196191
5×9543,22772,85000,320234234
5×12048,13411,55000,253268273
5×15055,04340,65000,206300311
5×18561,75329,52500,164342360
5×24068,66528,82500,125398427
5×30076,58248,52500,100457507
5×40086,210779,12500,0778529600
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×16+1020,5629,110001,91 – 3,08
4×25+1624,4880,010001,20 – 1,91112102
4×35+1626,91099,910000,868 – 1,91135126
4×50+2531,01418,610000,641 – 1,20158149
4×70+3536,91983,710000,443 – 0,868196191
4×95+5041,22569,310000,320 – 0,641234234
4×120+7046,43270,35000,253 – 0,443268273
4×150+7051,93944,45000,206 – 0,443300311
4×185+9558,24995,35000,164 – 0,320342360
4×240+12064,66184,42500,125 – 0,253398427
4×300+15072,47872,22500,100 – 0,206457507
4×400+18581,410091,12500,0778 – 0,164529600
Note :
Current carrying capacities are valid at 30°C ambient temperature