YAVZ2V , NAYRY                   AL/PVC/SWA/PVC
YAVZ2(a)V , NAYR(a)Y         AL/PVC/AWA/PVC
Voltage Rating
0.6/1 kV
Standards
TS IEC 60502-1 , VDE 0276
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Stranded Aluminum Conductor (Class 2)
Insulation
PVC (Polyvinyl Chloride)
Filler
PVC Filler
Armour
Round Steel Wire (Aluminium Wire for One Core Cables)
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:15D ( D : Overall Diameter )
Test Voltage:3,5 kV
Application:
For installation indoors and outdoors, in cable ducts, underground , in power or switching stations, local energy distribution
industrial plants, where there is no risk of mechanical damage.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×10*12,9240,610003,08
1×16*13,9281,710001,91
1×25*16,4392,610001,2010891
1×35*17,4450,710000,868129112
1×50*19,0518,710000,641153137
1×70*20,9639,410000,443187173
1×95*23,5814,010000,320223212
1×120*24,8928,710000,253252247
1×150*27,21101,710000,206280280
1×185*29,61301,610000,164314321
1×240*33,21639,35000,125358374
1×300*36,62048,75000,100397426
1×400*40,22505,15000,0778441488
1×500*43,93014,05000,0605489556
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1019,5781,210003,08
2×1622,21030,510001,91
2×2525,31332,510001,2010383
2×3527,41532,610000,868123101
2×5030,91894,810000,641145121
2×7036,22593,55000,443180155
2×9540,33197,95000,320216189
2×12044,23993,15000,253246220
2×15049,84847,85000,206276249
2×18554,45778,82500,164313287
2×24060,36883,32500,125362339
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1021,1940,710003,08
3×1623,21140,310001,91
3×2526,61479,510001,2010383
3×3529,01763,410000,868123101
3×5033,62317,810000,641145121
3×7038,42905,55000,443180155
3×9542,83630,65000,320216189
3×12047,44624,65000,253246220
3×15052,95541,12500,206276249
3×18557,96480,42500,164313287
3×24064,37693,22500,125362339
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×16+1024,41216,710001,91 – 3,08
3×25+1627,91566,010001,20 – 1,9110383
3×35+1629,91786,410000,868 – 1,91123101
3×50+2534,92445,310000,641 – 1,20145121
3×70+3539,73039,45000,443 – 0,868180155
3×95+5045,54131,15000,320 – 0,641216189
3×120+7049,74925,55000,253 – 0,268246220
3×150+7054,45713,82500,206 – 0,268276249
3×185+9560,26762,42500,164 – 0,320313287
3×240+12066,17893,22500,125 – 0,253362339
3×300+15074,510688,92500,100 – 0,206415401
3×400+18582,812677,72500,0778 – 0,164474468
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1022,61103,210003,08
4×1625,01337,310001,91
4×2528,91749,810001,2010383
4×3532,52269,910000,868123101
4×5037,02839,110000,641145121
4×7041,93482,15000,443180155
4×9548,44768,05000,320216189
4×12051,95469,35000,253246220
4×15058,06551,42500,206276249
4×18564,17627,02500,164313287
4×24070,79039,02500,125362339
4×30079,812293,22500,100415401
4×40088,514619,72500,0778474468
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1024,21252,310003,08
5×1627,11544,610001,91
5×2532,32203,510001,2010383
5×3535,92747,310000,868123101
5×5040,43372,85000,641145121
5×7046,94473,55000,443180155
5×9552,95712,15000,320216189
5×12056,76543,52500,253246220
5×15063,97758,52500,206276249
5×18570,29048,32500,164313287
5×24079,512168,52500,125362339
5×30087,814698,92500,100415401
5×40098,017798,42500,0778474468
Note 1:
* For YAVZ2(a)V , NAYR(a)Y cables
Note 2:
Current carrying capacities are valid at 30°C ambient temperature.