Açıklama

tds

Code
NYIFY-U       CU/PVC/PVC
Voltage Rating
300/500 V
Standards
VDE 0250 Teil 201
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Solid Copper Conductor (Class 1)
Insulation
PVC (Polyvinyl Chloride)
Filler
Armour
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:12D ( D : Overall Diameter )
Test Voltage:2 kV
Application
Suitable for dry and humid areas. All type of factory, warehouse and depots where there is fire and explosion threat. Not suitable for
underground. Used in fixed installations laying in conduit and under plaster.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×112,4 x 3,766,5100018,110
2×1,512,9 x 4,077,9100012,119
2×2,513,7 x 4,399,410007,4127
2×415,4 x 5,2141,510004,6134
2×616,4 x 5,7183,210003,08
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×117,0 – 3,792,0100018,110
3×1,517,7 x 4,0108,8100012,119
3×2,520,0 x 4,3141,410007,4127
3×422,4 x 5,2206,010004,6134
3×623,8 x 5,7267,110003,08
Note :
Current carrying capacities are valid at 30°C ambient temperature