Açıklama

tds

Code
H03VVH2-F, H05VVH2-F, A05VVH2-F    CU/PVC/PVC
Voltage Rating
300/300 V , 300/500 V
Standards
TS EN 50525-2-11Special Values
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Flexible Copper Conductor (Class 5)
Insulation
PVC (Polyvinyl Chloride)
Filler
Armour
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:6D ( D : Overall Diameter )
Test Voltage:300/300 V 1,5 kV , 300/500 V 2 kV
Application
These cables are used in dry places, pipes, flush-mounted or surface-mounted, indoor mobile installation cables in connection
or distribution.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×0,50**4,9 x 3,141,3100039,03
2×0,75**5,3 x 3,350,8100026,06
2×0,756,1 x 3,954,4100026,06
2×16,5 x 4,062,5100019,510
2×1,5*7,4 x 4,580,7100013,320
2×2,5*9,1 x 5,5125,910007,9827
2×4*10,3 x 6,2172,210004,9534
2×6*11,8 x 7,2240,110003,30
3×0,75*8,4 x 3,974,9100026,06
3×1*8,9 x 4,0486,7100019,510
3×1,5*10,5 x 4,5119,5100013,320
3×2,5*12,8 x 5,7184,510007,9827
3×4*14,5 x 6,4251,610004,9534
3×6*16,4 x 7,2341,510003,30
Note 1:
** For H03VVH2-F cables
* For A05VVH2-F cables
Note 2:
Current carrying capacities are valid at 30°C ambient temperature