Açıklama

tds

Code
H03V2H-H             CU/PVC
Voltage Rating
300/300 V
Standards
TS EN 50525-2-72
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Flexible Copper Conductor (Class 5)
Insulation
Filler
Armour
Sheath
Heat Resistance PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:6D ( D : Overall Diameter )
Test Voltage:1,5 kV
Application
This cables are used fixed installation cable in dry places, in pipes, under plaster or on plaster, in connection or distribution
facilities.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×0,505,5 x 2,521,5100039,03
2×0,755,8 x 2,728,5100026,06
Note :
Current carrying capacities are valid at 30°C ambient temperature