Açıklama

tds

Code
6241 Y , 6242 Y , 6243 Y     CU/PVC/PVC
Voltage Rating
300/500 V
Standards
BS 6004
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Solid Copper Conductor (Class 1)
Stranded Copper Conductor (Class 2)
Insulation
PVC (Polyvinyl Chloride)
Filler
Armour
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:12D ( D : Overall Diameter )
Test Voltage:2 kV
Application
Used as surface wiring where there is little mechanical damage risk or in conduit
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×1+15,2 x 4,147,010018,1 – 18,113
1×1,5+15,7 x 4,656,410012,1 – 18,116
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1+17,6 x 4,169,510018,1 – 18,113
2×1,5+18,4 x 4,690,810012,1 – 18,116
2×2,5+1,510,0 x 5,3128,11007,41 – 12,121
2×4+1,511,5 x 6,1184,81004,61 – 12,127
2×6+2,513,3 x 6,9238,51003,08 – 7,4134
2×6+414,0 x 6,9248,11003,08 – 4,6134
2×10+416,8 x 8,4380,51001,83 – 4,6145
2×10+617,0 x 8,4398,61001,83 – 3,0845
2×16+619,7 x 9,6546,21001,15 – 3,0857
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1+19,9 x 4,189,410018,1 – 18,113
3×1,5+111,2 x 4,6115,010012,1 – 18,116
3×2,5+113,1 x 5,3163,81007,41 – 18,121
3×4+1,515,8 x 6,3238,21004,61 – 12,127
3×6+2,517,9 x 6,9322,31003,08 – 7,4134
3×10+422,8 x 8,4506,41001,83 – 4,6145
3×16+626,8 x 9,6743,11001,15 – 3,0857
Note :
Current carrying capacities are valid at 30°C ambient temperature