Açıklama

tds

Code
CABT            AL/PVC/PVC
Voltage Rating
0.6/1 kV
Standards
TS IEC 60502-1
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Solid Aluminum Conductor (Class 1)
Stranded Aluminum Conductor (Class 2)
Insulation
PVC (Polyvinyl Chloride)
Filler
Armour
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:12D ( D : Overall Diameter )
Test Voltage:3,5 kV
Application:
It is used as energy, mains and lighting cable, in cable ducts outside, underground, where there is no risk of mechanical damage.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×108,5107,810003,08
1×169,5136,910001,91
1×2511,1188,010001,2010687
1×3512,1230,510000,868127107
1×5013,7280,310000,641151131
1×7015,7366,510000,443185166
1×9517,7478,610000,320222205
1×12019,2578,210000,253253239
1×15021,7708,910000,206284273
1×18524,0874,810000,164322317
1×24026,81101,710000,125375378
1×30029,81415,210000,100425437
1×40033,41797,310000,0778487513
1×50037,12205,05000,0605558600
1×63*15,7363,110000,456151131
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1015,0234,510003,08
2×1617,0297,810001,91
2×2520,1407,310001,2010282
2×3522,2497,810000,868123100
2×5025,3605,210000,641144119
2×7029,3803,310000,443179152
2×9533,41038,510000,320215186
2×12036,31245,410000,253245216
2×15041,41565,410000,206275246
2×18546,01916,410000,164313285
2×24051,52419,45000,125364338
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×6 re *13,9229,310004,74
3×1015,9297,110003,08
3×1618,0383,410001,91
3×2521,4535,810001,2010282
3×3523,7663,510000,868123100
3×5027,2811,210000,641144119
3×7031,51103,310000,443179152
3×9535,91434,710000,320215186
3×12039,11726,410000,253245216
3×15044,62170,15000,206275246
3×18549,62691,05000,164313285
3×24055,53402,75000,125364338
3×30062,04381,12500,100419400
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×16+1019,2449,110001,91 – 3,08
3×25+1622,6623,610001,20 – 1,9110282
3×35+1624,5747,610000,868 – 1,91123100
3×50+2528,5955,410000,641 – 1,20144119
3×70+3532,81268,010000,443 – 0,868179152
3×95+5037,61662,110000,320 – 0,641215186
3×120+7041,42038,25000,253 – 0,443245216
3×150+7046,02452,35000,206 – 0,443275246
3×185+9551,53070,25000,164 – 0,320313285
3×240+12057,33862,52500,125 – 0,253364338
3×300+15064,34963,42500,100 – 0,206419400
3×400+18572,26337,82500,0778 – 0,164484472
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1017,4365,610003,08
4×1619,8476,910001,91
4×2523,6673,210001,2010282
4×3526,1838,110000,868123100
4×5030,21045,310000,641144119
4×7035,11420,710000,443179152
4×9540,01851,910000,320215186
4×12043,52255,25000,253245216
4×15049,72829,85000,206275246
4×18555,33477,55000,164313285
4×24062,04433,02500,125364338
4×30069,25713,62500,100419400
4×40077,97315,32500,0778484472
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1019,0475,810003,08
5×1621,7626,910001,91
5×2525,9895,810001,2010282
5×3528,81136,410000,868123100
5×5033,51429,110000,641144119
5×7038,91944,95000,443179152
5×9544,42565,25000,320215186
5×12048,33085,25000,253245216
5×15055,23888,55000,206275246
5×18561,54823,72500,164313285
5×24068,96136,42500,125364338
5×30077,07928,72500,100419400
5×40086,710134,82500,0778484472
Note 1:
* Conductor resistance calculated theoretically.
Note 2:
Current carrying capacities are valid at 30°C ambient temperature.