Açıklama

tds

Code
ABC
Voltage Rating
0.6/1 kV
Standards
HD 626 S1
Conductor
Stranded Aluminium Conductor
Insulation:
XLPE (Cross Linked Polyethylene)
Construction
1 core: Straıght (marking)
2 core: Straıght (marking) – 1 Notch or number
3 core: Straıght (marking) – 1 Notch or number – 2 Notch or number
4 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number
5 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number – EP1 Straıght
5 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number – 4 Notch or number
6 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number – EP1 Straıght – EP2 1 Notch
6 core:1 Notch or number – 2 Notch or number – 3 Notch or number – 4 Notch or marking – EP1 Straıght – EP2 1 Notch
Technical Data
Max. Operating Temperature:90°C
Short  Circuit  Temperature:250°C (max.5 sec)
Operating Temperature: -40°C to +80°C
Bending Radius:12xD
Test Voltage:4.0 kV
Application:
Aerial Bundle Cable (ABC) low voltage cable for overhead power distribution offering higher level of safety and
reliability and lower power losses than bare conductors.
INSULATED WIRESMESSENGERFINISHED CABLE
Phase ConductorMain Distrubition Line
Nominal Cross SectionCross SectionDia.of ConductorResistance at 20°CCurrent Carrying CapacityCross SectionResistance
at 20°C
Dia.of ConductorMin.Tensile
Strenght
Resistance
at 20°C
Diameter Of CableNet Weight
mm²mm²mmohm/kmAmm²ohm/kmmmkNohm/kmmmkg/km
1×10103,73,085,742,8
1×16164,71,917,165,0
1×25255,91,208,598,7
1×35356,90,8689,5129,5
1×50508,10,64111,1173,3
1×63639,70,45612,7230,2
1×707010,00,44313,0238,6
1×959511,50,32014,9314,3
1×12012012,80,25316,2384,5
1×15015014,80,20618,2478,0
1×18518516,60,16420,2617,2
1×24024018,80,12522,8781,2
1×30030021,20,10025,6991,7
1×40040024,10,077828,51295,8
1×50050027,20,060532,01614,0
2×10103,73,0811,486,6
2×16164,71,9114,2131,6
2×25255,91,2016,9199,8
2×35356,90,86819,0263,6
2×50508,10,64122,2350,7
2×707010,00,44326,0482,9
2×959511,50,32029,8636,1
2×12012012,80,25332,5778,2
3×10103,73,0812,3130,4
3×16164,71,9115,3199,4
3×25255,91,2018,3301,7
3×35356,90,86820,5396,6
3×50508,10,64124,0526,7
3×707010,00,44328,0725,3
3×959511,50,32032,2955,4
3×12012012,80,25335,11168,7
4×10103,73,0813,8173,9
4×16164,71,9117,2266,0
4×25255,91,2020,5402,5
4×35356,90,86823,0529,2
4×50508,10,64126,8702,7
4×707010,00,44331,4967,8
4×959511,50,32036,01274,8
4×12012012,80,25339,31559,5
4×15015014,80,20644,11938,8
4×18518516,60,16448,82503,5
4×24024018,80,12555,13168,6
5×10103,73,0815,4217,5
5×16164,71,9119,1332,7
5×25255,91,2022,8503,4
5×35356,90,86825,6662,0
6×10103,73,0817,1261,2
6×16164,71,9121,2399,5
6×25255,91,2025,3604,5
INSULATED WIRESMESSENGERFINISHED CABLE
Phase ConductorMain Distrubition Line
Nominal Cross SectionCross SectionDia.of ConductorResistance at 20°CCurrent Carrying CapacityCross SectionResistance
at 20°C
Dia.of ConductorMin.Tensile
Strenght
Resistance
at 20°C
Diameter Of CableNet Weight
mm²mm²mmohm/kmAmm²ohm/kmmmkNohm/kmmmkg/km
3×16+25164,71,916,31,3818,3300,5
3×16+54,6164,71,919,50,63020,4415,1
3×25+16165,91,204,71,9119,6368,4
3×25+35255,91,207,40,98621,4433,9
3×25+54,6255,91,209,50,63022,9517,5
3×35+16356,90,8684,71,9123,0463,4
3×35+50356,90,8688,70,72024,3571,9
3×35+54,6356,90,8689,50,63024,8612,5
3×35+70356,90,86810,50,50025,6661,6
3×50+25508,10,6416,31,3825,5628,7
3×50+35508,10,6417,40,98626,2659,1
3×50+54,6508,10,6419,50,63027,7742,6
3×50+70508,10,64110,50,50028,5791,8
3×70+357010,00,4437,40,98629,6857,9
3×70+507010,00,4438,70,72030,6905,8
3×70+54,67010,00,4439,50,63031,1941,4
3×70+707010,00,44310,50,50032,0990,6
3×70+957010,00,44312,40,34333,11066,4
3×95+509511,50,3208,70,72034,11131,8
3×95+54,69511,50,3209,50,63034,61171,7
3×95+709511,50,32010,50,50035,41220,8
3×95+959511,50,32012,40,34336,61296,6
3×120+7012012,80,25310,50,50037,91435,4
3×120+9512012,80,25312,40,34339,01510,2
3×150+7015014,80,20610,50,50041,51718,8
3×150+9515014,80,20612,40,34342,61797,6
3×240+12024018,80,12512,80,25351,12766,3
4×25+16255,91,204,71,9122,1469,3
4×25+35255,91,206,90,86823,7534,9
4×35+16356,90,8684,71,9124,3596,1
4×35+25356,90,8685,91,2025,1630,3
4×50+25508,10,6415,91,2028,8804,8
4×95+259511,50,3205,91,2037,01377,9
INSULATED WIRESMESSENGERFINISHED CABLE
Phase ConductorMain Distrubition Line
Nominal Cross SectionCross SectionDia.of ConductorResistance at 20°CCurrent Carrying CapacityCross SectionResistance
at 20°C
Dia.of ConductorMin.Tensile
Strenght
Resistance
at 20°C
Diameter Of CableNet Weight
mm²mm²mmohm/kmAmm²ohm/kmmmkNohm/kmmmkg/km
3×25+54,6+1×16255,91,20161,919,50,63024,3584,4
3×35+50+1×16356,90,868161,918,70,72025,5643,3
3×35+54,6+1×16356,90,868161,919,50,63025,9679,5
3×35+54,6+1×25356,90,868251,209,50,63026,7713,7
3×50+25+1×16508,10,641161,916,31,3826,6695,2
3×50+35+1×25508,10,641251,207,40,98627,9760,3
3×50+54,6+1×16508,10,641161,919,50,63028,5809,8
3×50+70+1×25508,10,641251,2010,50,50030,0893,4
3×70+35+1×167010,00,443161,917,40,98630,3925,2
3×70+50+357010,00,443350,8688,70,72032,51038,0
3×70+54,6+1×167010,00,443161,919,50,63031,61008,7
3×70+95+1×257010,00,443251,2012,40,34334,11168,9
3×95+50+1×169511,50,320161,918,70,72034,31203,8
3×95+54,6+1×169511,50,320161,919,50,63034,71239,4
3×95+70+509511,50,320500,64110,50,50037,51396,7
3×120+70+1×1612012,80,253161,9110,50,50037,91501,9
3×120+95+7012012,80,253700,44312,40,34341,81751,8
3×25+54,6+2×16255,91,20161,919,50,63025,9651,3
3×25+54,6+2×25255,91,20251,209,50,63027,3719,5
3×35+54,6+2×16356,90,868161,919,50,63027,5746,8
3×35+54,6+2×25356,90,868251,209,50,63028,8815,0
3×35+70+2×16356,90,868161,9110,50,50028,2795,4
3×50+54,6+2×16508,10,641161,919,50,63029,9877,2
3×50+54,6+2×25508,10,641251,209,50,63031,2945,4
3×70+54,6+2×167010,00,443161,919,50,63032,71076,5
3×70+54,6+2×257010,00,443251,209,50,63034,01144,7
3×70+70+2×167010,00,443161,9110,50,50033,41125,7
3×70+70+2×257010,00,443251,2010,50,50034,81194,6
3×95+50+2×259511,50,320251,208,70,72036,51339,7
3×95+54,6+2×169511,50,320161,919,50,63035,51307,2
3×95+54,6+2×259511,50,320251,209,50,63036,91375,4
3×120+95+2×2512012,80,253251,2012,40,34340,51714,5
3×150+95+2×2515014,80,206251,2012,40,34343,51999,7
INSULATED WIRESMESSENGERFINISHED CABLE
Phase ConductorMain Distrubition Line
Nominal Cross SectionCross SectionDia.of ConductorResistance at 20°CCurrent Carrying CapacityCross SectionResistance
at 20°C
Dia.of ConductorMin.Tensile
Strenght
Resistance
at 20°C
Diameter Of CableNet Weight
mm²mm²mmohm/kmAmm²ohm/kmmmkNohm/kmmmkg/km
4×25+2×16255,91,20161,9123,9536
4×25+2×25255,91,20251,2025,3604,5
4×35+2×16356,90,868161,9126,0662,7
4×35+2×25356,90,868251,2027,4730,9
4×50+2×16508,10,641161,9129,2837,2
4×50+2×25508,10,641251,2030,5905,4
4×70+2×167010,00,443161,9132,91102,8
4×70+2×257010,00,443251,2034,31171
4×95+2×169511,50,320161,9136,71410,5
4×95+2×259511,50,320251,2038,11478,7
Note1:
The vein colors mentioned above may vary according to customer demand.
Note2:
Current carrying capacities are valid at 30°C ambient temperature.