Açıklama

tds

Code
A2XH-AF , AXZ1-AF                AL/XLPE/HFFR
Voltage Rating
0.6/1 kV
Standards
IEC 60228Conductor
EN 61034Smoke Density
EN 50267Halogen Free
EN 60332-3Flame Retardant (Cat C)
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Flexible Aluminum Conductor (Class 5)
Insulation
XLPE (Cross-linked Polyethylene)
Filler
Halogen Free Filler
Armour
Sheath
Halogen Free Sheath
Technical Data
Max. Operating Temperature:90°C
Short  Circuit  Temperature:250°C (max.5 sec)
Bending Radius:6D ( D : Overall Diameter )
Test Voltage:3,5 kV
Application:
Used in energy networks in refineries, mines, hotels, schools, tunnels, high constructions, hospitals, power plants, data processing
centers, business centers where there is a risk of fire.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×1,5*5,741,4100019,25
1×2,5*6,248,5100011,55
1×4*6,859,110007,22
1×6*7,369,410004,81
1×108,492,210003,08
1×169,2116,110001,91
1×2511,3167,610001,20114106
1×3512,3205,410000,868136130
1×5013,5256,610000,641162161
1×7015,6329,410000,443199204
1×9517,7424,010000,320238252
1×12019,6524,710000,253272295
1×15021,5637,610000,206305339
1×18523,9778,610000,164347395
1×24027,01003,910000,125404472
1×30029,51217,810000,100457547
1×40033,21551,710000,0778525643
1×50037,61924,95000,0605601754
1×63041,72429,85000,0469687882
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1,5*10,4143,3100019,25
2×2,5*11,3169,6100011,55
2×4*12,6210,010007,22
2×6*13,5254,110004,81
2×1015,8336,210003,08
2×1617,5420,110001,91
2×2521,5627,510001,20112102
2×3523,8778,110000,868135126
2×5026,5977,910000,641158149
2×7031,01311,910000,443196191
2×9534,91672,910000,320234234
2×12039,42122,210000,253268273
2×15043,22569,810000,206300311
2×18548,13184,410000,164342360
2×24054,24071,75000,125398427
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1,5*10,9154,5100019,25
3×2,5*11,8184,5100011,55
3×4*13,2229,910007,22
3×6*14,2280,510004,81
3×1016,7373,710003,08
3×1618,5472,810001,91
3×2522,9707,610001,20112102
3×3525,3883,410000,868135126
3×5028,31132,410000,641158149
3×7033,21512,410000,443196191
3×9537,51949,110000,320234234
3×12042,22443,210000,253268273
3×15046,32970,95000,206300311
3×18551,83698,65000,164342360
3×24058,54736,85000,125398427
3×30064,85858,22500,100457507
3×40072,97449,42500,0778529600
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×16+1019,7531,910001,91 – 3,08
3×25+1623,9772,310001,20 – 1,91112102
3×35+1625,9929,310000,868 – 1,91135126
3×50+2529,61228,710000,641 – 1,20158149
3×70+3534,51641,110000,443 – 0,868196191
3×95+5039,12112,610000,320 – 0,641234234
3×120+7044,42711,55000,253 – 0,443268273
3×150+7047,83184,15000,206 – 0,443300311
3×185+9553,63967,05000,164 – 0,320342360
3×240+12060,55087,65000,125 – 0,253398427
3×300+15066,76232,02500,100 – 0,206457507
3×400+18574,87852,52500,0778 – 0,164529600
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1,5*11,6175,5100019,25
4×2,5*12,7211,6100011,55
4×4*14,2266,310007,22
4×6*15,4327,210004,81
4×1018,2440,910003,08
4×1620,2563,610001,91
4×2525,1850,210001,20112102
4×3527,91066,310000,868135126
4×5031,31387,510000,641158149
4×7036,71852,610000,443196191
4×9541,62389,710000,320234234
4×12046,83017,35000,253268273
4×15051,33675,75000,206300311
4×18557,54566,35000,164342360
4×24065,05888,42500,125398427
4×30071,67186,92500,100457507
4×40080,69153,42500,0778529600
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1,5*12,5239,2100019,25
5×2,5*13,7287,1100011,55
5×4*15,4359,710007,22
5×6*16,6437,610004,81
5×1019,8590,510003,08
5×1622,0750,810001,91
5×2527,51129,210001,20112102
5×3530,71407,910000,868135126
5×5034,31798,910000,641158149
5×7040,52396,45000,443196191
5×9546,03062,65000,320234234
5×12051,83800,05000,253268273
5×15056,84666,25000,206300311
5×18563,65792,02500,164342360
5×24071,97473,42500,125398427
5×30079,39115,32500,100457507
5×40089,411665,82500,0778529600
Note 1:
* Conductor resistance calculated theoretically.Conductor resistances are taken from EN 60228 Class-2 Aluminum values.
Note 2:
Current carrying capacities are valid at 30°C ambient temperature.