Açıklama

tds

Code :
6181 YH   CU/PVC/PVC
Voltage Rating :
300/500 V
Standards :
BS 6004
IEC 60228Conductor
Reaction to Fire Classification ( CPR ) :
EN 60332-1-2Flame Retardant
Conductor :
Solid Copper Conductor (Class 1)
Stranded Copper Conductor (Class 2)
Insulation :
PVC (Polyvinyl Chloride)
Filler :
Armour :
Sheath :
PVC (Polyvinyl Chloride)
Technical Data :
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec.)
Bending Radius:12D ( D : Overall Diameter )
Test Voltage:2,0  kV
Application :
In dry rooms, switch and distribution boards,  for laying in conduit on and under plaster and on insulating supports
above plaster
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×1,5 re4,441,410012,116
1×1,5 rm4,543,710012,116
1×2,5 re4,955,91007,4121
1×2,5 rm5,259,51007,4121
1×4 re5,677,01004,6127
1×4 rm5,981,71004,6127
1×6 re6,199,11003,0834
1×6 rm6,5105,91003,0834
1×10 rm7,8153,610001,8345
1×16 rm9,0224,510001,1557
1×25 rm10,8339,710000,727
1×35 rm12,0438,510000,524
Note :
Current carrying capacities are valid at 30°C ambient temperature